The transformers of the DS0107 series have reinforced insulation and comply with the requirements of IEC 61558-1 / DIN EN 61558-1 (VDE 0570-1) and IEC 61558-2-15 DIN EN 61558-2-15 (VDE 0570-2-15).
In addition, the transformers comply with the requirements of IEC 60364-7-710 / DIN VDE 0100-710 (VDE 0100-710) for IT systems in medical locations. The windings are galvanically isolated. In order to minimize electrical interferences, an electrostatic screen is installed between the primary and secondary winding the lead out of which is connected to an insulated terminal for connection to the equipotential bonding.
The fixing angles are isolated from the transformer core in order to guarantee an isolated installation to comply with the requirements of DIN VDE 0100-710 (VDE 0100-710): 2002-11, para 710.512.1.6.2).
The transformers are available for horizontal and vertical installation. Protection against corrosion is guaranteed by a complete resin impregnation.
The transformers are designed for use in dry locations. Transformers of the SK2 series are completely encapsulated and fulfil the requirements of protection class II.
The transformers of the DS0107 series have reinforced insulation and comply with the requirements of IEC 61558-1 / DIN EN 61558-1 (VDE 0570-1) and IEC 61558-2-15 DIN EN 61558-2-15 (VDE 0570-2-15).
In addition, the transformers comply with the requirements of IEC 60364-7-710 / DIN VDE 0100-710 (VDE 0100-710) for IT systems in medical locations. The windings are galvanically isolated. In order to minimize electrical interferences, an electrostatic screen is installed between the primary and secondary winding the lead out of which is connected to an insulated terminal for connection to the equipotential bonding.
The fixing angles are isolated from the transformer core in order to guarantee an isolated installation to comply with the requirements of DIN VDE 0100-710 (VDE 0100-710): 2002-11, para 710.512.1.6.2).
The transformers are available for horizontal and vertical installation. Protection against corrosion is guaranteed by a complete resin impregnation.
The transformers are designed for use in dry locations. Transformers of the SK2 series are completely encapsulated and fulfil the requirements of protection class II.
Ordering information, Dimensions, Weight
Type | A | B | C | D | E | F | G | Cu weight | Weight | Art. No. |
---|---|---|---|---|---|---|---|---|---|---|
DS0107/2000 | 300 mm | 200 mm | 270 mm | 240 mm | 160 mm | 130 mm | 11 mm | 16 kg | 34 kg | B924694 |
DS0107/3150 | 360 mm | 210 mm | 325 mm | 310 mm | 170 mm | 135 mm | 11 mm | 28 kg | 63 kg | B924106 |
DS0107/4000 | 360 mm | 225 mm | 325 mm | 310 mm | 185 mm | 150 mm | 11 mm | 29 kg | 70 kg | B924121 |
DS0107/5000 | 360 mm | 240 mm | 325 mm | 310 mm | 200 mm | 165 mm | 11 mm | 31 kg | 77 kg | B924112 |
DS0107/6300 | 420 mm | 230 mm | 370 mm | 370 mm | 200 mm | 160 mm | 11 mm | 48 kg | 97 kg | B924107 |
DS0107/8000 | 420 mm | 245 mm | 370 mm | 370 mm | 215 mm | 175 mm | 11 mm | 51 kg | 107 kg | B924628 |
DS0107/10000 | 420 mm | 260 mm | 370 mm | 370 mm | 230 mm | 190 mm | 11 mm | 59 kg | 130 kg | B924672 |
DS0107/2000K | 300 mm | 310 mm | 240 mm | 162 mm | 130 mm | 11 mm | 16 kg | 34 kg | B924687 | |
DS0107/3150K | 360 mm | 360 mm | 310 mm | 170 mm | 135 mm | 11 mm | 28 kg | 63 kg | B924688 | |
DS0107/4000K | 360 mm | 360 mm | 310 mm | 185 mm | 150 mm | 11 mm | 29 kg | 70 kg | B924689 | |
DS0107/5000K | 360 mm | 360 mm | 310 mm | 200 mm | 165 mm | 11 mm | 31 kg | 77 kg | B924690 | |
DS0107/6300K | 420 mm | 420 mm | 370 mm | 200 mm | 160 mm | 11 mm | 48 kg | 97 kg | B924691 | |
DS0107/8000K | 420 mm | 420 mm | 370 mm | 215 mm | 175 mm | 11 mm | 51 kg | 107 kg | B924692 | |
DS0107/10000K | 420 mm | 420 mm | 370 mm | 230 mm | 190 mm | 11 mm | 59 kg | 130 kg | B924693 | |
DS0107/2000LG | 330 mm | 195 mm | 265 mm | 298 mm | 200 mm | 7 mm | 16 kg | 34 kg | B924695 | |
DS0107/3150LG | 394 mm | 198 mm | 310 mm | 358 mm | 240 mm | 9 mm | 28 kg | 63 kg | B924658 | |
DS0107/4000LG | 394 mm | 214 mm | 310 mm | 358 mm | 240 mm | 9 mm | 29 kg | 70 kg | B924659 | |
DS0107/5000LG | 394 mm | 228 mm | 310 mm | 358 mm | 240 mm | 9 mm | 31 kg | 77 kg | B924660 | |
DS0107/6300LG | 452 mm | 212 mm | 360 mm | 408 mm | 280 mm | 12 mm | 48 kg | 97 kg | B924661 | |
DS0107/8000LG | 452 mm | 227 mm | 360 mm | 408 mm | 280 mm | 12 mm | 51 kg | 107 kg | B924662 | |
DS0107/10000LG | 452 mm | 250 mm | 360 mm | 408 mm | 280 mm | 12 mm | 59 kg | 130 kg | B924679 | |
DS0107/2000SK2 | 410 mm | 190 mm | 400 mm | 380 mm | 330 mm | 125 mm | 11 mm | 16 kg | 49 kg | B924696 |
DS0107/3150SK2 | 520 mm | 190 mm | 450 mm | 490 mm | 390 mm | 135 mm | 11 mm | 28 kg | 75 kg | B924122 |
DS0107/4000SK2 | 520 mm | 190 mm | 450 mm | 490 mm | 390 mm | 135 mm | 11 mm | 29 kg | 80 kg | B924123 |
DS0107/5000SK2 | 520 mm | 200 mm | 450 mm | 490 mm | 390 mm | 150 mm | 11 mm | 31 kg | 86 kg | B924124 |
DS0107/6300SK2 | 520 mm | 200 mm | 500 mm | 490 mm | 450 mm | 150 mm | 11 mm | 48 kg | 107 kg | B924125 |
DS0107/8000SK2 | 520 mm | 215 mm | 500 mm | 490 mm | 450 mm | 175 mm | 11 mm | 51 kg | 130 kg | B924126 |
DS0107/10000SK2 | 520 mm | 230 mm | 500 mm | 490 mm | 450 mm | 175 mm | 11 mm | 59 kg | 155 kg | B924678 |
Nome | Tipo | Dimensione | Lingua | Timestamp | D-/B-Numero |
---|---|---|---|---|---|
ESL0107 - DS0107 | Dichiarazioni di conformità CE | 91.1 KB | 2022/08/1212.08.2022 | ||
DS0107 | Data sheet | 463.2 KB | DE | 2021/07/2828.07.2021 | D00105 |
DS0107 | Data sheet | 450.3 KB | EN | 2021/07/2828.07.2021 | D00105 |
DS0107 | Data sheet | 430.5 KB | ES | 2021/07/2828.07.2021 | D00105 |
Sicherheits-, Montage- und Wartungshaltungshinweise für Trenn-Transformatoren | Manuali di istruzioni | 699.6 KB | DE | 2022/06/1414.06.2022 | D00463 |
Safety, installation and maintenance instructions for isolating transformers | Manuali di istruzioni | 699.6 KB | EN | 2022/06/1414.06.2022 | D00463 |