- Prodotti
- Localizzazione guasti d'isolamento

ISOSCAN® EDS441
- Automatic insulation fault location
- Application control circuits
- 12 measuring channels for measuring current transformers
- CT connection monitoring
- Universal system concept
The insulation fault locators ISOSCAN® EDS441 are used in connection with the ISOMETER® iso685-D-P or the locating current injector PGH to locate insulation faults in unearthed power supply systems (IT systems).
They detect locating current signals generated by the insulation monitoring device iso685-D-P or the locating current injector PGH and evaluate them correspondingly. Up to 12 measuring current transformers can be connected to an EDS441. In total, up to 50 insulation fault locators can be connected via an RS-485 interface (BS bus protocol) and thereby up to 600 outgoing circuits can be monitored.
- Features
- Applications
- Accessories
- Ordering information
- Downloads
- Universal system concept
- Modular design, therefore easily adjustable to the given circumstances
- Measuring current transformers available in various sizes and versions
- CT connection monitoring
- 12 measuring channels for measuring current transformer series CTAC…, WS…, WS…-8000, W…AB
- Optional extension by 12 relay channels
- Fault memory behaviour selectable
- Up to 50 EDS insulation fault locators in the system, 600 measuring channels
- Response sensitivity 0.2…1 mA
- AC residual current measurement with configurable response value
- Two alarm relays with one N/O contact each
- N/O or N/C operation selectable
- External test/reset
- Central indication of faulty outgoing circuits
- Serial interface RS-485, BS bus address range 2…79, Modbus RTU
- Connection to higher-level control and visualisation systems possible
- Insulation fault location in AC, 3AC and DC IT systems
- Main circuits and control circuits in industrial plants and ships
- Diode-decoupled DC IT systems in power plants
- Systems for medical locations
Optional accessories for ISOSCAN® EDS441
Accessories
Measuring current transformer for EDS441
Alternative measuring current transformer from the Bender program
Type | Supply voltage US | Art. no. |
---|---|---|
DI-1PSM (RS-485 repeater) | AC/DC 24 V ± 20 % | B95012044 |
DI-2USB (interface converter RS-485/USB) with USB cable | Supplied by USB interface | B95012045 |
IOM441-S (Input/Output module) | 12-fold relay module | B95012057 |
AN471 (power supply unit for DI-1 or DI-2) | AC 230 V 50/60 Hz / AC, DC 20 V | B924189 |
Measuring current transformer for EDS441
Type | Internal diameter/mm | Design type | Art. no. |
---|---|---|---|
WS20x30-8000 | 20 x 30 | split-core | B98080602 |
WS50x80-8000 | 50 x 80 | split-core | B98080604 |
Alternative measuring current transformer from the Bender program
Type | Internal diameter/mm | Design type | Art. no. |
---|---|---|---|
W10/8000 | 10 | circular | B911759 |
W1-35/8000 | 35 | circular | B911756 |
W10/8000-6 | 10 | circular, 6-fold | B911900 |
WS20x30/8000 | 20 x 30 | split-core | B911764 |
WS50x80/8000 | 50 x 80 | split-core | B911757 |
Variants of ISOSCAN® EDS441
Type | Supply voltage US* | Response value | Art. no. |
---|---|---|---|
EDS441-S | AC/DC 24…240 V | 0.2…1 mA | B91080204 |
EDS441-L-4 | AC/DC 24…240 V | 0.2…1 mA | B91080205 |
EDS441-LAB-4 | AC/DC 24…240 V | 0.2…1 mA | B91080207 |
*Absolute values
Downloads for ISOSCAN® EDS441
Category | Prodotto | Language | Size | Download |
---|